Options in Decay chart tab

Editing field data for further inversion and resistivity mapping, namely:

Cutting off noisy tails


Deleting noisy decay segments (tails) is a standard procedure in TEM data preprocessing (Fig. 1). Select an end point at which to cut off the curve and press (Cut off all points after selected). Several curves of the same type can be edited simultaneously for better efficiency.

Example of noisy tail cut-off.
Fig. 1. Example of noisy tail cut-off.


Median filtering over several sweeps


Soundings are often run in duplicate or triplicate, etc., but only one decay is to be inverted. Median filtering several replica sweeps reduces noise and improves the data quality (Fig. 2). To apply median filtering, load two or more curves and press (Calculate average for active curves). After averaging, delete the original curves. For this first hide the resulting (median) curve: select the curve names in legend and press button (Delete active curves) (fig.3), then display the median curve.

Example median filtering EM Data
Fig. 2. Example median filtering of several sweeps. Step 1. Calculate median curve.

Example median filtering EM Data
Fig.3. Example median filtering of several sweeps. Step 2. Delete sweeps after having hidden median curve.


Splicing curves measured at different transmitter currents


Soundings may be run at the lowest or highest possible currents in order to extend the range of the transient process and minimize distortion from too long ramp time. For example, the minimum and maximum currents in the TEM equipment TEM Explorer (T1 transmitter) are 0.7-1.5 and 17-20 A, respectively. The responses at 1 A are the least distorted by the ramp time and bear high-quality information on the near-surface resistivity while those acquired at 13-15 A penetrate to greater depths. So, two such curves are spliced (Fig. 4) at the zone where they overlap at points selected by the user. If necessary, time correction is applied to the 13-15 A sounding to increase the overlap zone to the maximum.

Example of transient responses measured at low and high current and the spliced curve
Fig.4. Example of transient responses measured at 0.7 and 14 A (a) and the spliced curve (b).

For splicing, load two curves to Decay tab. Then select the splicing point where the two curves are the closest to one another (Fig. 5) and press Splice curves . The resulting decay will consist of the low-current response at early times and high-current response at later times. The original curves are deleted automatically.

Splicing TEM decays
Fig. 5. Splicing curves. Select splicing point and press Splice curves.